A fan's catalog curve assumes clean, straight, fully developed flow at the inlet and enough duct at the outlet to recover static pressure. Real mechanical rooms give it a 90° elbow one diameter from the inlet, a rectangular inlet box with a dead pocket, or an outlet elbow turning against wheel rotation. The gap between catalog and site is called system effect, and it's the most common reason a correctly selected fan under-delivers.

 

Inlet side: uniformity is everything

AMCA's rule of thumb is 3–5 duct diameters of straight duct before the inlet. Less than that and the wheel loads unevenly-one side works harder, the other stalls locally. Symptoms: reduced flow, raised power, blade-pass noise, vibration.

Worst offenders:

90° elbow right at the inlet​ without turning vanes → pre-rotating or counter-rotating swirl. Turning vanes fix most of it.
Inlet box mounted flush​ → dead cavity under the outlet where air hangs up. Reshape the box or add straightening vanes.
Side entry​ → air spins opposite the wheel, fan fights itself.
Free inlet with a wall too close​ → asymmetric loading, same as an elbow.

 

Outlet side: effective duct length

Air leaves a centrifugal scroll asymmetrically-pushed to the outer scroll, not uniform. It needs running duct to diffuse and regain static pressure. AMCA guidance: at least 2.5 duct diameters​ of effective outlet duct when velocity ≤ 13 m/s (2500 fpm); add one diameter for every extra 5 m/s (1000 fpm). At ~50% of effective length you get ~80% of the pressure regain.

An elbow too close to the outlet costs flow, and if it turns against wheel rotation the loss is worse than turning with it. Rule: keep 2–3 duct diameters before the first outlet elbow, or accept the penalty in the selection.

 

How to budget for it

System effect is not a fudge factor you discover at commissioning. It's a curve shift you put in during selection:

Inlet system effect​ → subtract from fan static pressure capability (curve drops).
Outlet system effect​ → add to required system pressure (system curve rises).
Both show up as "fan runs faster than calculated to hit design flow," then "motor runs out of amps," then "we oversized the motor."

The fix is cheap on paper and expensive on site: straight duct, turning vanes, inlet cones, outlet diffusers, adequate plenum depth. A properly shaped inlet cone can recover most of the loss a hard-edged inlet throws away.

 

What to write in the spec
Minimum straight duct at inlet (state diameters, not "as short as possible").
Elbow orientation relative to wheel rotation.
Inlet box geometry or cone type.
Effective outlet duct length before first elbow.
Whether backdraft dampers / silencers sit in the first 3 diameters (they add their own system effect).

MIDI Industrial's selection sheets include AMCA system-effect correction tables for common inlet/outlet configurations. Send us the mechanical room layout, not just the duty point-we'll flag the elbow that's eating your 15%.